Yn gyffredinol, nid yw'r hyd a argymhellir ar gyfer gwifrau digolledu thermocwl yn fwy na 100 metr. Y rheswm craidd am hyn yw osgoi ymwrthedd plwm gormodol, a all arwain at wanhad signal ac anghydbwysedd yn y graddiant tymheredd cyffordd oer, gan effeithio ar gywirdeb mesur tymheredd.
Specific adjustments should be made based on the application scenario: For typical industrial scenarios (such as normal temperature and short-to-medium distance transmission), a length of 50-100 meters is recommended. This range balances signal transmission stability with installation costs. For ultra-long distances (e.g., exceeding 100 meters), thicker core compensating leads (to reduce resistance) or shielded dedicated leads should be used, along with a low-input-impedance temperature measuring instrument to minimize signal loss. In high-temperature environments (>200 gradd ) neu senarios ag ymyrraeth electromagnetig cryf, dylid byrhau'r hyd ymhellach (a argymhellir Llai na neu'n hafal i 50 metr), a dylid gweithredu inswleiddiad gwres a cysgodi gwell i atal inswleiddio rhag heneiddio neu arosodiad signal ymyrraeth.
Gall mynd y tu hwnt i'r hyd penodedig arwain yn hawdd at y problemau canlynol:
① Gwanhau'r signal potensial thermodrydanol, gan arwain at werthoedd mesuredig is;
② Cynnydd graddiant tymheredd y dargludydd ei hun, gan arwain at fwy o wall iawndal cyffordd oer;
③ Mwy o dueddiad i signalau ymyrraeth mewn amgylcheddau electromagnetig cryf, gan effeithio ar sefydlogrwydd data. Mewn cymwysiadau ymarferol, dylid gwneud addasiadau yn unol â llawlyfr yr offeryn a nodweddion graddnodi thermocouple, gyda signalau mesuredig sefydlog fel y safon derfynol.